Commodore 5.7kVA Generator Shutdown Alarm Icons

The following icons, faults, descriptions and solutions will help to identify shutdown alarm icons for Commodore Air-Cooled Diesel Generators using the Smart Gen HGM1790N Controller

Shutdown alarms are latching and immediately stop the Generator. On initiation of the shutdown condition the module de-energises all the ‘Delayed Load Output’ and the ‘Close Gen Output’ outputs to remove the load from the generator.
 
Once this has occurred, the module shuts the generator set down immediately to prevent further damage. The alarm must be accepted and cleared, and the fault removed to reset the module.
 
Icon Fault Description Solution
Emergency Stop The emergency stop button has been depressed. This failsafe (normally closed to emergency stop) input and immediately stops the set should the signal be removed. 

-Has the emergency stop button been released?

-If the button has been realeased is it still displaying on the screen? if it is then  the switch is faulty

Fail To Start

The engine has failed to start after the configured number of start attempts 

-Does it have enough fuel?

-Is there any present fault codes preventing the generator from starting?

Fail To Stop

The engine has failed to stop after stop signals are made

- Press the red emergency stop button to stop, and re-start the generator

Low Oil Pressure

The module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired

-Does the generator need a service?

-Is there enough oil in the generator?

-Is the sensor plugged in properly?

Abnormal Voltage

Commonly associated with a low battery alarm caused by a trickle charger failure or not having an adequately sized trickle charger installed

- Is there a trickle charger always installed?

- Is the voltage of the battery lower than 12V as per a voltmeter?

- Is the trickle charger in an operating condition/working?

Engine High Temperature 

The module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired

- Has the generator been running for over 5 hours, particularly at 75% load or more?

- Is the temperature sensor over 6000Ω or under 5Ω?

- Has the generator been serviced recently?

Under Speed 

The engine speed has fallen below the under speed pre alarm setting  

-Is the generator getting enough fuel?

Over Speed 

The engine speed has risen above the over speed pre alarm setting 

-Is the engine rpm set correctly?
Charge Failure The auxiliary charge alternator voltage is low as measured from the W/L terminal

-Is the 12v alternator belt fitted correctly/not worn

-is the battery in good condition and not drawing too much power from the 12v alternator?

Low Fuel Level  The level detected by the fuel level sensor is below the low fuel level pre-set alarm setting -Is there enough fuel in the tank?
Generator Under Voltage  The generator output voltage has fallen below the pre-set alarm setting. after the Safety On timer has expired

-Has the voltage regulator been set correctly?

-Is the generator getting enough fuel?

-Has the generator rpm been set correctly?

Generator Over Voltage The generator output voltage has risen above the pre-set alarm setting

-Has the voltage regulator been set correctly?

-Has the generator rpm been set correctly?

Generator Over Current The measured current has risen above the configured trip level

- Decrease your energy usage 

- Wait for the generator to cool until starting again