The following icons, faults, descriptions and solutions will help to identify shutdown alarm icons for Commodore Air-Cooled Diesel Generators using the Smart Gen HGM1790N Controller
Icon | Fault | Description | Solution |
Emergency Stop | The emergency stop button has been depressed. This failsafe (normally closed to emergency stop) input and immediately stops the set should the signal be removed. |
-Has the emergency stop button been released? -If the button has been realeased is it still displaying on the screen? if it is then the switch is faulty |
|
Fail To Start |
The engine has failed to start after the configured number of start attempts |
-Does it have enough fuel? -Is there any present fault codes preventing the generator from starting? |
|
Fail To Stop |
The engine has failed to stop after stop signals are made |
- Press the red emergency stop button to stop, and re-start the generator |
|
Low Oil Pressure |
The module detects that the engine oil pressure has fallen below the low oil pressure pre-alarm setting level after the Safety On timer has expired |
-Does the generator need a service? -Is there enough oil in the generator? -Is the sensor plugged in properly? |
|
Abnormal Voltage |
Commonly associated with a low battery alarm caused by a trickle charger failure or not having an adequately sized trickle charger installed |
- Is there a trickle charger always installed? - Is the voltage of the battery lower than 12V as per a voltmeter? - Is the trickle charger in an operating condition/working? |
|
Engine High Temperature |
The module detects that the engine coolant temperature has exceeded the high engine temperature pre-alarm setting level after the Safety On timer has expired |
- Has the generator been running for over 5 hours, particularly at 75% load or more? - Is the temperature sensor over 6000Ω or under 5Ω? - Has the generator been serviced recently? |
|
Under Speed |
The engine speed has fallen below the under speed pre alarm setting |
-Is the generator getting enough fuel? |
|
Over Speed |
The engine speed has risen above the over speed pre alarm setting |
-Is the engine rpm set correctly? | |
Charge Failure | The auxiliary charge alternator voltage is low as measured from the W/L terminal |
-Is the 12v alternator belt fitted correctly/not worn -is the battery in good condition and not drawing too much power from the 12v alternator? |
|
Low Fuel Level | The level detected by the fuel level sensor is below the low fuel level pre-set alarm setting | -Is there enough fuel in the tank? | |
Generator Under Voltage | The generator output voltage has fallen below the pre-set alarm setting. after the Safety On timer has expired |
-Has the voltage regulator been set correctly? -Is the generator getting enough fuel? -Has the generator rpm been set correctly? |
|
Generator Over Voltage | The generator output voltage has risen above the pre-set alarm setting |
-Has the voltage regulator been set correctly? -Has the generator rpm been set correctly? |
|
Generator Over Current | The measured current has risen above the configured trip level |
- Decrease your energy usage - Wait for the generator to cool until starting again |