Commodore Generator Warning Alarm Icons

The following icons, faults, descriptions and solutions will help to identify warning alarm icons for Commodore Water-Cooled Diesel Generators using the Deep Sea 4620 controller

Commodore Generator warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition. By default, warning alarms are self-resetting when the fault condition is removed.
 
 
Icon Fault Description Solution
Auxiliary Inputs The module detects that an auxiliary input which has been user configured to create a fault condition has become active.   
Analogue Input Configured As Digital  The analogue inputs can be configured to digital inputs. The module detects that an input configured to create a fault condition has become active.  
Fail To Stop

The module has detected a condition that indicates that the engine is running when it has been instructed to stop.

NOTE: ‘Fail to Stop’ could indicate a faulty oil pressure sensor. If engine is at rest check oil sensor wiring and configuration. 

 
Charge Failure The auxiliary charge alternator voltage is low as measured from the W/L terminal.   
Low Fuel Level  The level detected by the fuel level sensor is below the low fuel level pre-set pre-alarm setting.   
High Fuel Level  The level detected by the fuel level sensor is above the high fuel level pre-set pre-alarm setting.  
Battery Under Voltage  The DC supply has fallen below or risen above the low volts pre-set pre-alarm setting.   
Battery Over Voltage The DC supply has risen above the high volts pre-set pre-alarm setting.   
Generator Under Voltage  The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired.  
Generator Over Voltage The generator output voltage has risen above the pre-set pre-alarm setting.   
Generator Under Frequency  The generator output frequency has fallen below the pre-set prealarm setting after the Safety On timer has expired.  
Generator Over Frequency The generator output frequency has risen above the pre-set prealarm setting.  
Immediate Over Current The measured current has risen above the configured trip level.  
Delayed Over Current The measured current has risen above the configured trip level for a configured duration.   
Oil Filter Maintenance Alarm Maintenance due for oil filter.   
Air Filter Maintenance Alarm  Maintenance due for air filter   
Fuel Filter Maintenance Alarm Maintenance due for fuel filter  
Magnetic Pickup Open Circuit Magnetic pickup sensor has been detected as being open circuit.  
Loss Of Mag. Pickup Signal The speed signal from the magnetic pickup is not being received by the DSE controller.