The following icons, faults, descriptions and solutions will help to identify warning alarm icons for Commodore Water-Cooled Diesel Generators using the Deep Sea 4620 controller
Commodore Generator warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition. By default, warning alarms are self-resetting when the fault condition is removed.
Icon | Fault | Description | Solution |
Auxiliary Inputs | The module detects that an auxiliary input which has been user configured to create a fault condition has become active. | ||
Analogue Input Configured As Digital | The analogue inputs can be configured to digital inputs. The module detects that an input configured to create a fault condition has become active. | ||
Fail To Stop |
The module has detected a condition that indicates that the engine is running when it has been instructed to stop. NOTE: ‘Fail to Stop’ could indicate a faulty oil pressure sensor. If engine is at rest check oil sensor wiring and configuration. |
||
Charge Failure | The auxiliary charge alternator voltage is low as measured from the W/L terminal. | ||
Low Fuel Level | The level detected by the fuel level sensor is below the low fuel level pre-set pre-alarm setting. | ||
High Fuel Level | The level detected by the fuel level sensor is above the high fuel level pre-set pre-alarm setting. | ||
Battery Under Voltage | The DC supply has fallen below or risen above the low volts pre-set pre-alarm setting. | ||
Battery Over Voltage | The DC supply has risen above the high volts pre-set pre-alarm setting. | ||
Generator Under Voltage | The generator output voltage has fallen below the pre-set pre-alarm setting after the Safety On timer has expired. | ||
Generator Over Voltage | The generator output voltage has risen above the pre-set pre-alarm setting. | ||
Generator Under Frequency | The generator output frequency has fallen below the pre-set prealarm setting after the Safety On timer has expired. | ||
Generator Over Frequency | The generator output frequency has risen above the pre-set prealarm setting. | ||
Immediate Over Current | The measured current has risen above the configured trip level. | ||
Delayed Over Current | The measured current has risen above the configured trip level for a configured duration. | ||
Oil Filter Maintenance Alarm | Maintenance due for oil filter. | ||
Air Filter Maintenance Alarm | Maintenance due for air filter | ||
Fuel Filter Maintenance Alarm | Maintenance due for fuel filter | ||
Magnetic Pickup Open Circuit | Magnetic pickup sensor has been detected as being open circuit. | ||
Loss Of Mag. Pickup Signal | The speed signal from the magnetic pickup is not being received by the DSE controller. |